This MPO 12F OS2 to LC simplex breakout cable connects one MPO-12/APC female connector to twelve individual LC/UPC connectors. Its twelve single-mode fibers are intended for separate LC panel positions. Choose this configuration when each fiber needs its own termination and identification; confirm the complete connection map before ordering.
Product Overview
The supplied configuration uses OS2 9/125 μm fiber and a yellow jacket. The LC ends are simplex: each connector terminates one fiber. Twelve LC connectors therefore mean twelve fiber terminations, not twelve duplex circuits. Where two fibers form one transmit/receive pair, the pairing must be recorded in the system design rather than inferred from the connector count.
This page specifies the yellow, female-MPO assembly. The MPO breakout and harness cable range is the starting point for other fiber counts, branch connectors and paired LC formats. Use the product drawing to identify the selected build; a family description alone does not approve an order.
Key Features
- One MPO-12/APC female end and twelve LC/UPC simplex terminations.
- Twelve OS2 fibers for individually assigned panel positions.
- Separate LC ends for layouts that do not use fixed duplex clips.
- Yellow cable identification in the supplied product specification.
- An order review focused on branch numbering, destination ports and dimensional references.
Technical Specifications
The configuration identity below comes from the supplied product brief. Commercial options and performance limits require an approved BWNFiber build sheet.
| Item | Configuration or confirmation required |
|---|---|
| Product family | MPO breakout / harness cable |
| Populated fibers | 12 |
| MPO connector | MPO-12/APC female; confirm key orientation and mating connector |
| Branch connectors | 12 × LC/UPC simplex |
| Fiber class | OS2 single-mode, 9/125 μm; specific fiber standard requires confirmation |
| Jacket color | Yellow in the supplied configuration |
| Overall length | Source lists 1–50 m; availability, reference points and tolerance: confirmation with BWNFiber |
| Fanout length | Source lists 30 / 45 / 60 cm and a 30 cm default; accepted drawing dimensions: confirmation with BWNFiber |
| Jacket options | Source lists LSZH / OFNP / OFNR; construction, applicable rating and supporting documents: confirmation with BWNFiber |
| Polarity | Source lists Type A / B / C; exact MPO position-to-LC identity map: confirmation with BWNFiber |
| Insertion loss / return loss | No numeric limits approved for this SKU: confirmation with BWNFiber |
| Mechanical limits | Cable/branch diameters, installation bend radius, tensile limits and operating temperature: confirmation with BWNFiber |
Testing and acceptance documents
Request the approved optical acceptance sheet for this assembly. It should identify the applicable wavelengths, test reference method, acceptance limits, connector interfaces and recorded results. A component insertion-loss figure and an end-to-end assembly loss are different quantities; ask which one the quotation specifies before comparing suppliers.
For twelve separately routed ends, the continuity record should connect every LC label to its MPO position. Record the drawing revision and assembly identity with the report so the installation team can match the delivered cable to the approved map. End-face inspection criteria and the scope of any supplied test records are confirmation with BWNFiber. This page does not claim that a test report has already been issued.
The source names TIA/EIA-568.3-D, IEC 61754-7, IEC 61754-20, IEC 61753-1, IEC 61300-3-4 and RoHS. These references are not evidence that the selected assembly has been tested, certified or declared compliant. Applicable editions, clauses, test methods and declarations are confirmation with BWNFiber. The fiber testing overview provides general background; the purchase specification must contain the actual acceptance requirements.
Selection Guidance
Check the termination format first
| Requirement | Selection direction | Check before releasing the order |
|---|---|---|
| Twelve individually assigned single-mode LC positions | This simplex configuration | Every branch label and destination port |
| Six paired LC connections | Evaluate the duplex OS2 configuration | Pair arrangement, clips and routing |
| A specified G.657.A2 fiber and black LSZH jacket | Request a separately documented configuration | Fiber declaration and assembly bend limits; color alone is insufficient |
| A pinned MPO mating arrangement | Request the appropriate male-MPO configuration | Actual opposite connector, keying and polish |
| An eight-active-fiber parallel-optics application | Select by exact module and channel requirements | Populated positions, endpoint compatibility and host breakout support |
Confirm both connector interfaces
Female MPO refers to the unpinned connector. Check the actual connector on the opposite side of the mating point; an adapter description alone does not identify that connector’s pin state. Record key orientation and the required face finish as separate fields.
APC at the MPO end and UPC at the LC end describe two different interfaces on this cable. They do not authorize mating APC and UPC faces together at the same connection. The LC destination must accept the specified LC/UPC interface.
Approve the twelve-branch map
Label each branch and assign a destination. For every branch, record: LC branch ID, MPO position, destination panel/port, circuit or pair reference, and verification result. Do not assume branch label 1 is wired to MPO position 1 unless the approved drawing says so.
Drawing release check
Check that all twelve positions are accounted for once, with no duplicate branch assignments or unexplained unused positions. Compare the map with both endpoint records. A Type A/B/C selection is not a substitute for this branch-level identification. The MPO polarity checklist covers the wider channel review without expanding this product page into a polarity tutorial.
Applications
- Single-mode distribution frames with independently assigned LC/UPC positions.
- Panel layouts where individual fiber labels must follow separate destinations.
- Documented MPO-to-LC transitions within an approved data center cabling design.
These are selection scenarios, not customer case studies or interoperability approvals. A passive harness routes fibers; it does not itself convert a protocol or guarantee a data rate. Do not purchase this full twelve-fiber configuration as a generic DR4 or PSM4 cable without checking the exact equipment interface, active positions, optical budget and required topology.
Order Guide
Provide the configuration identity once, then specify its options. The source lists 13 lengths, three polarity choices and three jacket choices. The tables below preserve those requested option values without repeating the full product name across 117 rows. They do not confirm that every combination is commercially available.
| Field | Requested value |
|---|---|
| Assembly | MPO-12/APC female to 12 × LC/UPC simplex, 12F OS2, yellow |
| Polarity | A / B / C as a request; attach the approved branch map |
| Jacket | LSZH / OFNP / OFNR as a request; state the installation requirement |
| Fanout | 30 / 45 / 60 cm from source, or submit a dimensioned request |
| Quantity and destination | State units, ship-to country and required delivery date |
| Documentation | State drawing revision, labeling schedule and required acceptance records |
| Nominal length (m) | Approximate length (ft) |
|---|---|
| 1 | 3.28 |
| 1.5 | 4.92 |
| 2 | 6.56 |
| 3 | 9.84 |
| 5 | 16.40 |
| 7 | 22.97 |
| 10 | 32.81 |
| 15 | 49.21 |
| 20 | 65.62 |
| 25 | 82.02 |
| 30 | 98.43 |
| 40 | 131.23 |
| 50 | 164.04 |
Metric dimensions govern the request; feet are conversions rounded to two decimals. Define overall length between named reference planes. For staggered ends, identify which branch establishes the overall dimension and give each leg its own length. Do not add a fanout length to the quoted overall length unless the drawing uses that convention.
Custom lengths, 0.9 mm legs, staggered branches, pulling eyes and special labels are source-listed requests whose feasibility is confirmation with BWNFiber. The supplied ordering pattern is BWN-BO-M12APCF-12LCSX-OS2-YEL-{POL}-{JKT}-{LEN}; it is a proposed pattern, not an approved SKU. Obtain the final part number and configuration revision in the quotation. MOQ, samples, lead time and delivery terms are confirmation with BWNFiber.
Why Source from BWNFiber
Use the inquiry to establish whether the proposed build meets your panel layout and acceptance requirements. Ask BWNFiber to confirm the twelve-branch drawing, approved materials, available test documentation and final commercial offer. These records provide a concrete basis for comparing proposals and checking repeat orders.
Before an order is repeated, compare the requested configuration against the last approved revision. Changes to fiber specification, pinning, jacket, branch length or labels should be visible in the revised build sheet. Do not infer production capability or certification from this product description.
Need a Configuration Review or Sample?
Send your MPO mating-interface details, twelve destination LC ports, branch map, overall and fanout dimensions, jacket requirement, quantity and delivery destination. Ask for a confirmed configuration, available sample arrangement and quotation before purchase.