Product Summary
This high-fiber-count indoor cable uses stranded 12-fiber subunits around an FRP central strength member. The supplied BWNFiber record lists 24F, 36F, 48F, 72F, 96F, 144F and 168F constructions with PVC or LSZH jacket options. Count-specific outside diameter, weight, tensile load and bend-radius values are provided for configuration review.
The record describes a cable body, not a complete connectorized MPO trunk. It does not define installed connectors, polarity, gender, key orientation, pinning, end-face polish or finished-assembly insertion/return loss. Those fields must be specified separately if the quotation includes a terminated MPO assembly.
For wider product selection, compare the indoor fiber cable range. For connectorized links, use the fiber cable assembly configuration hub or the data center MPO cabling section.
Short Answer for Buyers
Use this product record when the approved design calls for a stranded, multi-unit indoor cable with 12F subunits, an FRP central member and a total count from 24F to 168F. Select the exact count first, then match its outside diameter and weight to the route and handling plan. Do not treat this cable-body record as proof of a finished MPO connector configuration or a specific fire rating.
Quick Configuration Check
| Buyer requirement | What to select or confirm |
|---|---|
| Total fiber count | Choose one recorded count: 24F, 36F, 48F, 72F, 96F, 144F or 168F |
| Subunit plan | 12 fibers per subunit; confirm the subunit map on the approved drawing |
| Fiber grade | Choose one listed single-mode or multimode grade; do not combine rows |
| Jacket | PVC or LSZH, subject to the approved project specification |
| Route fit | Check the count-specific outside diameter against pathway, gland, clamp and pulling limits |
| Finished MPO assembly | TBC — define connector ends, polarity, gender, pinning, polish, length and acceptance limits |
| Required evidence | Approved datasheet, construction drawing and test/acceptance plan |
Key Features
- Seven recorded fiber-count configurations from 24F to 168F.
- Stranded construction based on 12F subunits.
- FRP central strength member with aramid yarn in the subunits.
- PVC or LSZH jacket options.
- Recorded single-mode and multimode fiber-grade alternatives.
- Count-specific cable diameter, weight, tensile load and bend-radius values for RFQ comparison.
Cable Construction
| Component | Recorded specification | Evidence status |
|---|---|---|
| Total fiber count | 24F, 36F, 48F, 72F, 96F, 144F or 168F | BWNFiber internal record F0532; exact source row/datasheet required for release |
| Subunit | 12 colored 250 μm fibers with aramid yarn | Internal record plus supplied construction image; approved drawing required |
| Central strength member | FRP | Internal record and supplied construction image |
| Cable lay | Stranded multi-unit construction | Internal record and supplied construction image |
| Outer jacket | PVC or LSZH | Internal record; any fire-rating claim requires separate evidence |
| Armor / water blocking | TBC — not established by the supplied evidence | Do not infer |
| Installed MPO connectors | TBC — not shown or specified | Source required if sold as a finished assembly |
Mechanical Specifications by Fiber Count
| Fiber count | 12F subunits* | Cable outside diameter | PVC weight | LSZH weight | Tensile load, long/short term | Crush load | Bend radius, dynamic/static |
|---|---|---|---|---|---|---|---|
| 24F | 2 | Ø9.6 ± 0.3 mm | 64 kg/km | 72 kg/km | 150/500 N | TBC — source required | 20D/10D |
| 36F | 3 | Ø9.6 ± 0.3 mm | 64 kg/km | 72 kg/km | 150/500 N | TBC — source required | 20D/10D |
| 48F | 4 | Ø9.6 ± 0.3 mm | 64 kg/km | 72 kg/km | 150/500 N | TBC — source required | 20D/10D |
| 72F | 6 | Ø11.3 ± 0.3 mm | 92 kg/km | 103 kg/km | 150/500 N | TBC — source required | 20D/10D |
| 96F | 8 | Ø13.3 ± 0.3 mm | 129 kg/km | 146 kg/km | 150/500 N | TBC — source required | 20D/10D |
| 144F | 12 | Ø15.5 ± 0.3 mm | 160 kg/km | 250 kg/km | 150/500 N | TBC — source required | 20D/10D |
| 168F | 14 | Ø15.5 ± 0.3 mm | 150 kg/km | 250 kg/km | 150/500 N | TBC — source required | 20D/10D |
*Subunit quantity is the arithmetic result of total fiber count divided by the recorded 12 fibers per subunit. Confirm the exact lay and identification sequence on the approved construction drawing. D is the selected cable’s outside diameter.
Specification notice: recorded figures are configuration-specific reference values, not universal guarantees. Confirm the current BWNFiber datasheet, drawing revision, test method and order record before using them in a contract, installation plan or acceptance checklist.
Fiber Options and Recorded Optical Characteristics
Choose one fiber grade for each configuration. Values in different rows are alternatives and must not be combined.
| Fiber grade | Wavelength | Typical attenuation | Maximum attenuation | OFL bandwidth at 850/1300 nm | Effective modal bandwidth at 850 nm |
|---|---|---|---|---|---|
| G.657.A1 | 1310/1550 nm | 0.36/0.22 dB/km | 0.5/0.4 dB/km | — | — |
| G.657.A2 | 1310/1550 nm | 0.36/0.22 dB/km | 0.5/0.4 dB/km | — | — |
| 50/125 μm | 850/1300 nm | 3.0/1.0 dB/km | 3.5/1.5 dB/km | ≥500/500 MHz·km | — |
| 62.5/125 μm | 850/1300 nm | 3.0/1.0 dB/km | 3.5/1.5 dB/km | ≥200/500 MHz·km | — |
| OM3 | 850/1300 nm | 3.0/1.0 dB/km | 3.5/1.5 dB/km | ≥1500/500 MHz·km | ≥2000 MHz·km |
| OM4 | 850/1300 nm | 3.0/1.0 dB/km | 3.5/1.5 dB/km | ≥3500/500 MHz·km | ≥4700 MHz·km |
These are fiber-level values recorded in the supplied draft. They are not finished MPO assembly insertion-loss, return-loss or application-reach guarantees. BWNFiber should attach the approved fiber specification or product datasheet before release.
Mechanical and Environmental Conditions
| Condition | Recorded range or requirement |
|---|---|
| Transportation, storage and operation | −20 °C to +60 °C |
| Installation | −5 °C to +50 °C |
| Dynamic bend radius | 20 × selected cable outside diameter |
| Static bend radius | 10 × selected cable outside diameter |
| Tensile/crush test method | TBC — source required |
| Regional flame classification | TBC — source required |
“LSZH” identifies a jacket-material option in the supplied record. It does not by itself prove a specific OFNR, OFNP, CPR, IEC or other flame-test classification.
Interface Boundary: Cable Body vs Finished MPO Assembly
This record can define the cable body used in an MPO assembly, but it cannot define the finished link. If BWNFiber is asked to supply a terminated trunk, the quotation and drawing must also specify:
- Connector family and fiber position count at each end.
- Male/pinned or female/unpinned configuration.
- Key orientation, polarity method and complete fiber map.
- UPC or APC polish where applicable.
- Finished length, breakout/furcation design and tolerance.
- Pulling-eye or protective-hardware requirements.
- Finished-assembly insertion-loss and return-loss limits.
- End-face, polarity and optical-test methods and report format.
All connector and finished-assembly test fields are TBC — source required for this product.
How to Select the Correct Configuration
- Confirm whether the purchase is for bulk cable or a finished MPO cable assembly.
- Choose the total fiber count from the recorded 24F–168F options and confirm the corresponding 12F-subunit plan.
- Select one fiber grade that matches the approved optical design.
- Select PVC or LSZH according to the project specification; request separate rating evidence when required.
- Check the count-specific outside diameter, weight, bend radius and tensile values against the route and handling plan.
- If the cable will be terminated, freeze the complete connector, polarity, gender, pinning, polish, breakout and test requirements.
- Approve the final datasheet, construction drawing, BOM and acceptance plan before production.
Difference from the Compact 12F/24F Indoor Cable Product
The 24F option on this page is not interchangeable with BWNFiber’s separate compact 12F/24F cable record.
| Attribute | This 24F–168F multi-unit product | Separate compact 12F/24F product |
|---|---|---|
| Primary role | Higher-count stranded multi-unit cable body | Compact 12F/24F cable body |
| Construction | 12F subunits + aramid yarn + FRP central member + stranded outer cable | Colored 250 μm fibers + aramid yarn + outer jacket |
| 24F outside diameter | Ø9.6 ± 0.3 mm | Ø3.6 ± 0.2 mm |
| 24F tensile load, long/short | 150/500 N | 50/150 N |
| Substitution rule | Match the full BOM, structure and route limits | Do not substitute by the shared 24F label |
Use Cases and Boundaries
Supported by the supplied record:
- Indoor fiber distribution using the recorded multi-unit construction.
- Cable-body input for an MPO assembly after the connectorized design is separately approved.
- Routes that remain within the recorded diameter, tensile, bend and temperature conditions.
Not established by the supplied evidence: outdoor exposure, direct burial, aerial installation, armor, water blocking, UV resistance, rodent resistance, a specific flame rating, plenum/riser listing, connector compatibility, polarity, finished-assembly IL/RL or transmission reach.
Testing and Quality-Control Requirements
The supplied record does not identify cable test methods or finished-assembly acceptance limits. Before release or purchase, BWNFiber and the buyer should agree on:
- Approved product datasheet and construction drawing revision.
- Fiber-grade certificate or source specification.
- Cable diameter, length, marking and visual-inspection criteria.
- Tensile, bend and crush test methods when contractually required.
- Subunit identification and fiber-map check.
- For a terminated assembly: polarity map, end-face inspection, insertion-loss and return-loss limits, and report format.
Packaging and Procurement Information
Packaging format, standard reel/drum length, minimum order quantity, production lead time, warranty and destination-specific export documentation are TBC — BWNFiber confirmation required. Do not infer these commercial terms from another cable family.
Required Information for an RFQ
Send the following information for a configuration review and quotation:
- Bulk cable or finished MPO assembly.
- Total fiber count: 24F, 36F, 48F, 72F, 96F, 144F or 168F.
- Selected fiber grade.
- PVC or LSZH jacket and any separately required fire classification.
- Total length, length per drum/roll/assembly and quantity.
- Route constraints, maximum allowable outside diameter and installation environment.
- Cable marking, labeling, packaging and delivery destination.
- Required datasheet, drawing, certificate and test-report format.
- If terminated: both-end connector details, polarity, gender/pinning, key orientation, polish, breakout design, finished length and IL/RL limits.
Downloads Required Before Publication
- Product datasheet: TBC — approved source required.
- Cable construction and subunit map drawing: TBC — approved source required.
- Cable test method / acceptance plan: TBC — approved source required.
- Finished-assembly polarity and IL/RL report template: TBC — only if supplied as a terminated assembly.