MPO Cable Types: Trunk vs Breakout vs Harness vs Patch Cord vs Loopback (2026 Guide)

Complete guide to MPO cable types: trunk, breakout, harness, patch cord, loopback. Learn MPO vs MTP, Base-8/12/16/24, polarity Type A/B/C, and how to choose for 400G/800G data centers.

A few years ago, a data center contractor in Germany called me at 11 p.m. They had just unpacked 200 MPO trunk cables for a 400G spine-leaf rollout — and half of them were the wrong polarity. The project stopped for three days. The cost of rework, labor, and delayed commissioning ran past €40,000.

The mistake was not the cable quality. It was ordering the right family (MPO) but the wrong type and configuration.

MPO cables are not interchangeable. A trunk cable carries all fibers straight through. A breakout cable splits an MPO into discrete connectors. A patch cord is a short jumper. A loopback is a test device. Choosing the wrong type leaves you with unmated ports, extra adapters, or a loss budget that does not close.

In this guide, I will explain each MPO cable type, when to use it, and how to avoid the most common ordering mistakes. By the end, you will be able to pick the correct cable type, fiber count, and polarity for your project — and write a BOM that your supplier cannot misread.

Quick Decision Tree

Use this tree to select the right cable type in under 60 seconds.

MPO cable type decision tree for selecting trunk, breakout, fanout, harness, patch cord, jumper, or loopback cables
Decision tree showing which MPO cable type to select based on whether the application requires panel-to-panel trunking, LC breakout, splicing, cassette patching, short rack connections, or transceiver testing.

MPO vs MTP®: What’s the Real Difference?

This is the most common point of confusion for buyers.

MPO (Multi-fiber Push-On) is the generic industry standard for multi-fiber connectors defined in IEC 61754-7.

MTP® is a registered trademark of US Conec. It is a high-performance version of the MPO connector.

FeatureGeneric MPOMTP®
StandardIEC 61754-7IEC 61754-7 compatible
FerruleStandard compositeFloating ferrule, often metal pin clamp
Insertion lossStandard grade (≤ 0.75 dB typical)Elite grade (≤ 0.35 dB available)
DurabilityStandardHigher durability, removable housing
IntermateabilityYesFully intermateable with MPO
MPO vs MTP connector comparison showing generic MPO and branded MTP connector design and performance differences
Side-by-side technical comparison of generic MPO and MTP connectors, explaining standards, housing design, ferrule system, insertion-loss options, and intermateability.

The simple rule: all MTP® connectors are MPO connectors, but not all MPO connectors are MTP®. For most data center applications, a quality generic MPO cable is sufficient. For ultra-low-loss links or frequent reconfiguration, MTP® Elite is worth the premium.

BWNFiber supplies both generic MPO and MTP®-compatible assemblies. We default to IEC 61754-7 compliant ferrules and can ship US Conec MTP® Elite connectors on request.

MPO Fiber Count: Base-8, Base-12, Base-16, Base-24

MPO connectors come in several fiber counts. The count you choose must match your transceiver’s lane count, or you will waste fibers or buy the wrong optics.

BaseFiber CountTypical BreakoutCommon Optics
Base-88 fibers4× LC duplex40G SR4, 100G SR4, 400G DR4
Base-1212 fibers6× LC duplexLegacy structured cabling, 40G/100G
Base-1616 fibers8× LC duplex or 2× MPO-8400G SR8, 800G SR8/DR8
Base-2424 fibers12× LC duplex or 2× MPO-12High-density patch fields
Comparison of MPO Base-8, Base-12, Base-16, and Base-24 fiber counts for 40G, 100G, 400G, and 800G optics
Technical infographic comparing MPO fiber counts, active lanes, unused fibers, breakout configurations, connector keying, and typical 40G, 100G, 400G, and 800G applications.

Why Base-8 Dominates Modern 400G/800G

Base-8 matches the 8 lanes used by 400G DR4 and 800G SR8/DR8 transceivers. There are no unused fibers.

Base-12 was the default for 40G/100G SR4, but it leaves 4 fibers idle when breaking out to 4 duplex lanes. In a large deployment, those idle fibers add cost and complexity.

Base-16 is purpose-built for 800G parallel optics. MPO-16 uses an offset key and is not physically compatible with MPO-12. Always verify your transceiver datasheet before ordering.

Project case: In 2024, BWNFiber supplied Base-8 MPO trunks for a hyperscale data center in Singapore upgrading to 400G. By switching from Base-12 to Base-8, the customer reduced fiber waste by approximately 30% and simplified polarity management across 1,200+ links.

Planning a 400G or 800G rollout? Send us your transceiver datasheet. We will map each port to the correct Base-8 or Base-16 MPO cable and polarity.

MPO Polarity Explained: Type A, B, C

Polarity defines how fiber positions at one end map to positions at the other end. Get it wrong, and your transmit fibers connect to other transmit fibers instead of receive fibers.

PolarityMappingBest For
Type AStraight-through (1→1, 2→2…)Legacy duplex systems, one A→B patch cord at one end
Type BReversed (1→12, 2→11…)40G/100G/400G/800G parallel optics (most common)
Type CPair-flipped (1→2, 2→1…)Older duplex deployments
MPO polarity Type A, Type B, and Type C fiber mapping diagram showing straight-through, reversed, and pair-flipped connections
Fiber mapping diagram explaining MPO Type A straight-through polarity, Type B reversed polarity, and Type C pair-flipped polarity for structured cabling and parallel-optics links.

Type B Is the Default for Data Centers

For parallel optics (SR4, SR8, DR4, DR8), Type B is the standard. It naturally swaps Tx/Rx pairs, so you can use the same patch cord type on both ends of a link.

Male vs Female Connectors

Every mated MPO pair must have one male connector (with guide pins) and one female connector (without pins). A common mistake is ordering two females or two males for the same link.

  • Transceiver ports are usually male (pinned).
  • Patch panels / cassettes are usually female (unpinned).
  • Cables should be ordered to match what they connect to.
MPO male vs female connector comparison showing guide pins, guide holes, and correct male-to-female mating
Technical comparison showing pinned male MPO connectors and unpinned female MPO connectors, including correct and incorrect mating combinations.

BWNFiber practice: we laser-mark polarity type and gender on both ends of every trunk cable. This reduces field wiring errors by roughly 60% based on customer feedback.

Not sure about your polarity scheme? Send us your transceiver list and channel diagram. We will review your MDA-to-HDA links and recommend Type A, B, or C for each route.

MPO Trunk Cable

An MPO trunk cable has the same MPO connector on both ends and passes all fibers straight through. It is the backbone of modern structured fiber cabling in data centers.

Typical Construction

AttributeCommon Value
Fiber count8, 12, 16, 24, 32, 48
Fiber typeOM3, OM4, OM5, OS2
JacketOFNP, LSZH, OFNR
PolarityType A, B, or C
Length3 m to 300 m
Insertion loss≤ 0.35 dB (low-loss), ≤ 0.75 dB (standard)
MPO trunk cable structure showing MPO connectors, cable body, labeling, pulling eye, and panel-to-panel backbone application
Technical illustration of an MPO-to-MPO trunk cable with configurable fiber count, jacket, polarity, pulling eye, and use between data center distribution areas.

When to Use

  • Backbone links between distribution areas (MDA to HDA)
  • Inter-rack or inter-row trunking in spine-leaf architectures
  • Pre-terminated main cabling before breakout to servers

Real Project Case

In 2024, BWNFiber supplied 140 MPO-12 OM4 trunks, 30 m average length, for a financial services data center in Singapore. The project used Type B polarity throughout the MDA-to-HDA links. Installation time was reduced by approximately 40 percent compared to field-terminated LC assemblies.

MPO Breakout Cable

An MPO breakout cable splits one MPO connector into multiple simplex or duplex connectors, usually LC or SC.

Typical Construction

AttributeCommon Value
Breakout end4, 6, 8, 12 LC duplex pairs
MPO end8, 12, 16, 24 fiber
Breakout length0.5 m to 2.0 m
Breakout boot2.0 mm or 0.9 mm fanout tubing

When to Use

  • Direct connection from an MPO switch port to individual 10G/25G server ports
  • Bypassing a cassette to save insertion loss
  • Rack-top-of-rack (ToR) deployments where space is tight

400G to 8×50G Example

A 400G SR8 QSFP-DD transceiver has an MPO-16 interface. An MPO-16 to 8×LC duplex breakout cable lets you fan out to eight 50G SFP56 ports. This is common in migration scenarios where some downstream ports remain at lower speeds.

MPO-16 to eight LC duplex breakout mapping for 400G and 800G parallel-optics applications
Lane-mapping diagram showing how a 16-fiber MPO interface can break out into eight LC duplex connections for high-speed parallel-optics applications.

MPO Fanout Cable

MPO fanout cables are similar to breakout cables but often have unconnectorized legs or are designed for splicing inside enclosures.

Typical Construction

AttributeCommon Value
Fanout legs0.9 mm buffered fiber
Connector optionsLC, SC, ST, or unterminated
Use locationSplice trays, ODFs, fiber enclosures

When to Use

  • Transitioning from MPO backbone to individual fiber management
  • Splicing into existing ODF infrastructure
  • Custom-length legs where pre-terminated LC breakouts are too rigid

Difference from breakout: a breakout cable is usually fully connectorized for direct plug-and-play. A fanout cable is often used as a transition element inside equipment.

MPO Harness Cable

An MPO harness cable is a compact breakout designed to plug directly into high-density cassettes or patch panels. The legs are short and precisely length-controlled.

Typical Construction

AttributeCommon Value
Leg length0.3 m to 1.0 m
Leg countMatches cassette port count
ConnectorLC duplex, often with push-pull tabs

When to Use

  • Inside MPO-LC cassettes
  • Interconnecting panels where cable routing is predefined
  • Situations where strain relief and bend radius must be tightly controlled
MPO breakout vs fanout vs harness cable comparison showing connector ends, branch lengths, and typical applications
Three-way comparison explaining how MPO breakout, fanout, and harness cables differ in connectorization, branch construction, leg length, and installation use.

MPO Patch Cord

An MPO patch cord is a short MPO-to-MPO cable used for interconnecting panels, switches, and test equipment.

Typical Construction

AttributeCommon Value
Length0.5 m to 10 m
Fiber count8, 12, 16
JacketOFNP, LSZH
PolarityType A or B

When to Use

  • Patch panel to switch connections
  • Test setups
  • Rack-to-rack interconnections under 10 m

MPO fiber jumper: Many suppliers use “jumper” and “patch cord” interchangeably. For procurement clarity, specify length, fiber count, polarity, and jacket rating rather than relying on the product name. BWNFiber treats “jumper” as a patch cord under 1 m.

MPO Fiber Jumper

An MPO fiber jumper is essentially a very short MPO patch cord, usually under 1 m, used inside racks or cabinets. In practice, many suppliers use “jumper” and “patch cord” interchangeably, so the safest approach is to specify length, fiber count, polarity, and jacket rating rather than relying on the product name.

Typical Construction

AttributeCommon Value
Length0.3 m to 1.0 m
Fiber count8, 12, 16
JacketOFNP, LSZH
PolarityType A or B

When to Use

  • Connections between adjacent panels inside the same rack
  • Inside fiber shelves or cable managers where space is tight
  • Equipment loop management where extra cable length adds clutter

BWNFiber practice: we treat “jumper” as any MPO patch cord under 1 m. If you need a precise intra-rack length, send us the panel spacing and we will cut the exact length with the correct polarity and gender.

Need help with a rack layout? Send your panel spacing and transceiver list. We will recommend the right jumper length, fiber count, and polarity for each link.

MPO Loopback Module

An MPO loopback module routes transmit fibers back to receive fibers, creating a closed optical loop for testing.

Typical Construction

AttributeCommon Value
Fiber count8 or 16
Return mappingTx fibers looped to Rx fibers
HousingCompact plastic or metal

When to Use

  • Transceiver burn-in testing
  • Switch port diagnostics
  • OTDR and optical power meter loop tests
  • Production line quality verification

Example: a switch manufacturer may use an MPO-16 loopback to verify all 8 Tx/Rx pairs on an 800G SR8 port before shipping the chassis.

Comparison of MPO trunk, breakout, fanout, harness, patch cord, jumper, and loopback cable types
Visual comparison of seven MPO cable configurations, showing connector ends, cable structure, and primary applications for data center and telecom networks.

Breakout Cable vs Cassette: Which Saves More Loss?

A common design question is whether to use a breakout/harness cable directly or a trunk cable plus MPO-LC cassette.

FactorBreakout / Harness CableTrunk + Cassette
Insertion lossLower (one MPO connection)Higher (two MPO connections)
FlexibilityLower (fixed legs)Higher (easy moves/adds/changes)
Cable managementMore complex at equipment endCleaner, organized
CostLower material costHigher material cost
Best forFixed, permanent connectionsDynamic, frequently reconfigured environments
MPO breakout cable vs MPO-LC cassette comparison showing connection points, insertion-loss impact, cable management, and flexibility
Comparison of direct MPO breakout connections and trunk-plus-cassette architectures, focusing on connection count, optical loss, cable management, cost, and reconfiguration flexibility.

Rule of thumb: If the port mapping is unlikely to change, use a breakout or harness cable to save ~0.5 dB of loss. If you expect frequent reconfigurations, use a cassette.

Comparison Table

Cable TypeEnd AEnd BPrimary UseBest For
TrunkMPOMPOBackbone linksPanel-to-panel, structured cabling
BreakoutMPOLC/SC × NDirect port fanoutSwitch to server, migration
FanoutMPOUnterminated/LC/SCSplice transitionEnclosure, ODF
HarnessMPOLC × N (short legs)Cassette patchingHigh-density panels
Patch CordMPOMPOShort interconnectsRack patching, tests
JumperMPOMPOVery short intra-rackAdjacent panels
LoopbackMPOLoopbackTestingTransceiver/switch diagnostics

How to Choose: Application Mapping

ApplicationRecommended Cable TypeNotes
Spine-to-leaf trunkMPO trunkType B, low-loss
Leaf switch to server NICMPO breakoutMPO-12 to 4×LC duplex for 40G SR4
400G SR8 switch portMPO patch cord or trunkMPO-16, Type B
800G SR8/DR8 switch portMPO trunk or breakoutMPO-16 or MPO-8, Type B
Fiber cassette internalMPO harnessMatch cassette port layout
ODF splice transitionMPO fanoutLeave legs unterminated if splicing
New data center backbonePre-terminated MPO trunkFactory-tested, labeled
Transceiver burn-inMPO loopback8-fiber for 100G SR4, 16-fiber for 800G SR8
MPO cable application mapping for spine-leaf links, switch breakout, cassettes, ODF splicing, and transceiver testing
Application map showing which MPO cable type is recommended for spine-to-leaf trunks, switch-to-server breakouts, cassettes, ODF transitions, short patching, and optical testing.

Common Mistakes When Ordering

  1. Specifying “breakout” when you need “trunk”
    A trunk is MPO-to-MPO. A breakout is MPO-to-discrete. Mixing these causes rework.

  2. Ordering the wrong Base
    Base-12 does not match 400G/800G parallel optics cleanly. Use Base-8 or Base-16 for modern high-speed links.

  3. Ignoring polarity
    Type B is the default for parallel optics. Pick one method for the whole channel and document it.

  4. Wrong connector gender
    Every mated pair needs one male and one female. Check your transceiver port gender before ordering.

  5. Ordering the wrong fanout leg length
    Breakout and fanout cables need leg lengths that match your rack depth and cable manager.

  6. Mismatched fiber counts
    An MPO-12 breakout cannot feed eight 50G lanes from a 400G SR8 transceiver. You need MPO-16.

  7. Forgetting the jacket rating
    Plenum (OFNP) is required in air-handling spaces. LSZH is common in Europe and Asia. Riser (OFNR) is acceptable in vertical shafts.

  8. Mating UPC and APC polish
    Never mate UPC and APC connectors. APC is for single-mode. UPC is for multimode.

Eight common MPO cable ordering mistakes including wrong cable type, fiber count, polarity, connector gender, leg length, jacket, and polish
Procurement infographic explaining eight common MPO cable specification errors and the checks buyers should complete before placing an order.

Installation & Maintenance Tips

After 10 years of supplying MPO assemblies, here is what we tell every field team:

  1. Plan polarity and gender before touching a cable. Print a channel diagram and give it to the installer.
  2. Maintain bend radius. During installation, keep bend radius ≥ 20× cable diameter. Long-term, ≥ 10×.
  3. Use Velcro straps, never zip ties. Zip ties crush fiber and add microbending loss.
  4. Label both ends. Include cable ID, destination, fiber count, and polarity.
  5. Clean before mating. Use a one-click MPO cleaner on both the connector and the transceiver port. One dirty ferrule can contaminate multiple channels.
  6. Test every channel. Use an OLTS (Tier 1) on every fiber. For trunks longer than 50 m, add OTDR (Tier 2) to locate faults.
MPO cable installation and maintenance checklist covering polarity, bend radius, Velcro straps, labeling, cleaning, and optical testing
Six-step installation and maintenance guide for MPO assemblies, including polarity verification, bend-radius control, cable management, labeling, end-face cleaning, and optical testing.

Standards & Compliance

BWNFiber MPO cable assemblies are manufactured and tested to the following standards where applicable:

  • IEC 61754-7 — MPO connector interface standard
  • TIA-568.3-D — Optical fiber cabling components standard
  • ITU-T G.651.1 / G.652.D / G.657.A1 — Multimode and single-mode fiber specifications
  • IEC 60332 / IEC 60754 — LSZH flame and halogen requirements
  • NFPA 262 — Plenum (OFNP) flame propagation

Every assembly is 100% tested for insertion loss (IL) and return loss (RL). Test reports are available on request.

MPO cable quality-control process showing end-face inspection, cleaning, insertion-loss testing, return-loss testing, polarity verification, and labeling
Quality-assurance workflow for MPO cable assemblies, covering connector inspection, cleaning, insertion-loss and return-loss testing, polarity verification, labeling, and test-report generation.

International Procurement Notes

Different regions have different preferences and compliance requirements for MPO cabling. Here is what BWNFiber typically sees in export orders:

Region / MarketCommon RequirementsNotes
North AmericaOFNP plenum, TIA-568.3-D, UL-listed jacketsData centers often require plenum-rated trunks for air-handling spaces.
EuropeLSZH jacket, CE marking, REACH / RoHS complianceHalogen-free and low-smoke jackets are widely specified for indoor routes.
Middle EastUV-resistant outer jacket, high-temp compoundOutdoor trunks and duct runs need UV and thermal aging resistance.
Southeast AsiaLSZH or PE jacket, humidity / fungus resistanceCoastal or tropical sites often specify anti-fungal cable grease.
Africa ISP / FTTHFlexible MOQ, simplified packaging, cost-optimizedProjects often prioritize fast delivery and clear labeling over premium grades.
OEM / ODMCustom jacket color, connector color, label, reelBWNFiber supports laser-marked logos, part numbers, and barcoded labels.

Logistics reminder: MPO assemblies are precision components. For sea freight, we use moisture-barrier packaging and shock-absorbing reels. For air freight, we confirm reel dimensions and weight before booking.

Planning a multi-region rollout? Send us the destination list and local standards. We will recommend the right jacket, fiber grade, and certification package for each site.

Buyer Checklist

Before you request a quote, confirm the following items. Sending a complete specification reduces back-and-forth and avoids rework.

Cable Definition

  • [ ] Cable type: trunk / breakout / fanout / harness / patch cord / jumper / loopback
  • [ ] Fiber count: 8 / 12 / 16 / 24 / 32 / 48
  • [ ] Fiber type: OM3 / OM4 / OM5 / OS2
  • [ ] Length per cable or total footage
  • [ ] Connector type on each end: MPO male / MPO female / LC / SC / unterminated
  • [ ] Polarity: Type A / Type B / Type C

Environment & Compliance

  • [ ] Installation location: indoor plenum / indoor riser / outdoor duct / aerial
  • [ ] Jacket requirement: OFNP / LSZH / OFNR / PE / UV-resistant
  • [ ] Regional certification: CE / REACH / RoHS / UL / local telecom approval
  • [ ] Flame or halogen requirement

Performance & Testing

  • [ ] Loss grade: standard (≤ 0.75 dB) / low-loss (≤ 0.35 dB) / elite (≤ 0.25 dB)
  • [ ] Return loss requirement
  • [ ] End-face inspection standard
  • [ ] IL/RL test report required per cable or per batch

Logistics & Customization

  • [ ] Quantity and acceptable MOQ
  • [ ] Required delivery date
  • [ ] Reel or packaging preference
  • [ ] Labeling: part number, destination, polarity, fiber count
  • [ ] Pulling eyes needed? (common on long trunks)
  • [ ] Samples required before production?

BWNFiber can review your BOM before quoting. Send the checklist above with your rack layout or transceiver list and we will flag any mismatch before production.

MPO cable buyer checklist covering cable type, fiber count, polarity, jacket, optical performance, testing, packaging, and delivery
Buyer checklist summarizing the technical, environmental, performance, logistics, labeling, testing, and customization information required for an accurate MPO cable quotation.

FAQ

What is the difference between MPO and MTP®?

MPO is the generic multi-fiber connector standard. MTP® is US Conec’s high-performance brand of MPO. They are fully intermateable, but MTP® typically offers lower insertion loss and higher durability.

What is Base-8 vs Base-12 vs Base-16?

Base-8 has 8 fibers, Base-12 has 12 fibers, Base-16 has 16 fibers. Base-8 is best for 40G/100G/400G parallel optics with no wasted fibers. Base-16 is used for 400G SR8 and 800G SR8/DR8.

What polarity type is most common for MPO cables?

Type B is the most common for modern data centers because it naturally swaps Tx/Rx pairs for parallel-optic links.

Can I use a Base-12 MPO cable with a 400G transceiver?

Physically it can mate, but it leaves 4 fibers unused. For 400G/800G, use Base-8 or Base-16 to match the transceiver lane count.

What is the difference between APC and UPC polish?

APC (Angled Physical Contact) is used for single-mode to minimize back-reflection. UPC (Ultra Physical Contact) is used for multimode. Never mate APC with UPC.

What is the difference between MPO trunk and MPO backbone?

There is no structural difference. “Backbone” simply describes the role in the cabling topology. Both are typically MPO-to-MPO pass-through cables.

Can I use a breakout cable instead of a cassette?

Yes, if the cable length, bend radius, and strain relief fit your rack layout. Breakout cables can save the insertion loss of a cassette but are less flexible for moves, adds, and changes.

What is the typical insertion loss of an MPO cassette?

A standard MPO-LC cassette adds approximately 0.75 dB to 1.0 dB of insertion loss. Low-loss cassettes can be under 0.35 dB.

When should I choose harness over breakout?

Choose harness when the breakout legs must be short, uniform, and routed inside a cassette or panel. Choose breakout for direct switch-to-server runs.

What is a pulling eye on an MPO trunk?

A pulling eye is a temporary metal or composite loop attached to the cable end for installation. It protects the connectors during pulling through conduit. It is removed after installation.

Can MPO loopbacks test polarity?

MPO loopbacks confirm optical continuity and transceiver function, but they do not verify correct fiber mapping. Use a polarity tester for mapping verification.

How do I clean an MPO connector?

Use a one-click MPO cleaner on both the connector end-face and the transceiver port. Clean every time before mating, even for new cables.

Does BWNFiber provide test reports with MPO cables?

Yes. Every BWNFiber MPO assembly is 100% tested for insertion loss and return loss. IL/RL test reports and end-face inspection images are available on request.

Get a Quote for Your MPO Cable Type

BWNFiber supplies all MPO cable types in custom lengths, fiber counts, and polarity configurations.

Standard product range:

  • MPO trunk, breakout, fanout, harness, patch cord, jumper, and loopback
  • OM3, OM4, OM5, OS2
  • 8/12/16/24/32 fiber counts
  • APC and UPC polish
  • OFNP, LSZH, OFNR jackets
  • MTP® Elite and generic MPO options
  • Custom labeling, pulling eyes, and packaging

BWNFiber advantages:

  • Factory-tested IL/RL on every assembly
  • Custom polarity and gender configurations
  • Project support from BOM review to installation guidance
  • Samples available for qualification testing

Send us your rack layout, transceiver list, or BOM. We will recommend the correct cable type, polarity, fiber count, and loss grade for each link — and provide a sample and test report for evaluation (subject to BWNFiber sample policy).

BWNFiber custom MPO cable quotation banner showing trunk, breakout, patch cord, and loopback cable options
Call-to-action banner inviting data center buyers and engineers to submit a BOM, rack layout, or transceiver list for MPO cable type, polarity, fiber-count, and loss-grade review.

[email protected]
www.bwnfiber.com

  • MPO vs MTP: Complete Guide for Data Center Managers
  • 400G MPO Cable: Base-8 vs Base-16 Selection Guide
  • 800G MPO Cable: What You Need to Know
  • MPO Polarity Guide: Type A, B, C Explained
  • BWNFiber MPO Cable Product Page